A Comprehensive Guide to Charging Your Refrigeration System with Freon Gas

Refrigeration systems are devices that transfer heat from a lower temperature region to a higher temperature region, using a working fluid called refrigerant. The refrigerant undergoes phase changes from liquid to vapor and back to liquid as it circulates through the system, absorbing and releasing heat. One of the most common refrigerants used in refrigeration systems is freon gas, which is a generic term for a group of chlorofluorocarbons (CFCs) or hydrochlorofluorocarbons (HCFCs).

Example of provision refrigeration system onboard vessel

Maintaining and servicing a refrigeration system requires careful attention to detail, especially when it comes to charging the system with the right amount of Freon gas. The performance and efficiency of a refrigeration system depend largely on the amount and quality of the refrigerant in the system. Too much or too little refrigerant can cause problems such as reduced cooling capacity, increased energy consumption, compressor damage, and environmental pollution. Therefore, it is important to charge the refrigeration system with the correct amount and type of refrigerant, following proper procedures and safety precautions.

In this comprehensive guide, we’ll walk you through the step-by-step process of charging your refrigeration system with Freon gas, including the proper use of a recovery bottle, which is a device that collects and stores the excess or contaminated refrigerant from the system. We’ll also delve into potential problems that might arise during charging and provide troubleshooting tips to help you identify and resolve issues effectively.

Understanding the Importance of Proper Charging

Properly charging a refrigeration system is essential to ensure its efficient cooling capacity and prevent potential problems such as reduced performance, increased energy consumption, and even compressor failure.

Icing evaporator

Overcharging or undercharging the system can lead to serious issues, including decreased cooling efficiency, frost formation on evaporator coils, and potential damage to components due to inadequate lubrication.

Step-by-Step Guide to Charging with Freon Gas

  • Gather the Necessary Equipment: Before you begin the charging process, ensure you have the required tools and equipment, including a recovery machine, a recovery bottle, a pressure gauge, a charging hose with a manifold gauge set, and the appropriate type and amount of Freon gas. To learn more about EU-regulation related to the type of Freon approved to use, please follow THIS LINK.
  • Recover Existing Refrigerant (if needed): If you’re working on an existing system, you might need to recover any remaining refrigerant. Use a recovery machine to safely remove the old refrigerant from the system and store it in a recovery bottle according to environmental regulations. To learn more about refrigerant regulations, please follow THIS LINK.
  • Prepare the System: Ensure that the refrigeration system is turned off and has equalized in pressure. Connect the manifold gauge set to the system’s low and high-pressure ports.
  • Attach the Charging Hose: Connect the charging hose from the manifold gauge set to the refrigerant supply cylinder, ensuring a secure and leak-free connection.
  • Purge the Charging Hose: Before connecting the charging hose to the system, carefully purge it to eliminate any air or contaminants. This can be done by briefly opening the hose valves and allowing a small amount of refrigerant to escape before closing them again.
  • Charge the System: Slowly open the valve on the refrigerant supply cylinder and begin charging the system. Monitor the pressure gauges on the manifold gauge set to ensure that the system’s pressures are within the recommended range for the specific refrigerant type and ambient conditions.
  • Monitor Superheat and Subcooling: As the system charges, keep an eye on the superheat (for evaporator coil) and subcooling (for condenser coil) temperatures. Adjust the charging process accordingly to achieve the recommended superheat and subcooling values for the specific refrigerant and system.
  • Seal and Disconnect: Once the system is properly charged and the pressures and temperatures are stable, close the valve on the refrigerant supply cylinder. Disconnect the charging hose from the system’s ports and securely close the manifold gauge valves.
  • Check for Leaks: It’s crucial to perform a leak check to ensure that there are no refrigerant leaks in the system. Use a refrigerant leak detector or a soap solution to check for any escaping gas.

Liquid Recovery Method

The liquid recovery method is one of the most common and efficient methods of charging a refrigeration system with freon gas. In this method, the refrigerant is transferred while still in the liquid state, which minimizes the loss of refrigerant and reduces the charging time. The liquid recovery method can be used for most types of refrigeration systems, regardless of the metering device (such as TXV, capillary tube, or piston).

Recovery method schematic example. Source and credit: http://www.endocrinologue-agadir.ma

To perform the liquid recovery method, you will need the following tools and equipment:

  • A manifold gauge set with hoses and valves
  • A recovery machine with a filter-drier

    Example of a recovery machine

  • A recovery bottle with a float switch
  • A digital scale
  • A vacuum pump
  • A thermometer or a temperature clamp
  • A pressure-temperature (PT) chart for the type of refrigerant you are using
  • Personal protective equipment such as gloves and goggles

The steps for the liquid recovery method are as follows:

  1. Turn off the power supply to the refrigeration system and disconnect it from the power source.
  2. Connect the manifold gauge set to the service ports of the system. The high-pressure gauge (red) should be connected to the liquid line service port, and the low-pressure gauge (blue) should be connected to the suction line service port. Make sure that both valves on the manifold are closed.
  3. Connect the recovery machine to the manifold gauge set. The inlet port of the recovery machine should be connected to the center hose of the manifold, and the outlet port of the recovery machine should be connected to another hose.
  4. Connect the recovery bottle to the outlet hose of the recovery machine. The recovery bottle should have a float switch that automatically shuts off the recovery machine when it reaches 80% of its capacity. This prevents overfilling and possible explosion of the bottle.
  5. Connect the digital scale to the recovery bottle and place it on a flat surface. The digital scale will measure the weight of the refrigerant that is transferred from the system to the bottle.
  6. Connect the vacuum pump to another hose and attach it to either one of the service ports on the system. The vacuum pump will remove any air or moisture from the system before charging.
  7. Open both valves on the manifold gauge set and turn on the vacuum pump. Evacuate the system until it reaches a vacuum level of at least 500 microns. This may take several minutes depending on the size and condition of the system.
  8. Close both valves on the manifold gauge set and turn off the vacuum pump. Disconnect it from the service port and cap it with a protective cap.
  9. Turn on the recovery machine and open only the high-pressure valve on the manifold gauge set. This will allow liquid refrigerant to flow from the system to the recovery bottle through the recovery machine.
  10. Monitor the pressure readings on the gauges, the weight reading on the scale, and the temperature reading on the thermometer or the clamp. The pressure readings should decrease as the refrigerant leaves the system, and the weight reading should increase as the refrigerant enters the bottle. The temperature reading should be close to the saturated liquid temperature for the type of refrigerant you are using, which you can find on the PT chart.
  11. Continue the recovery process until you reach the desired amount of refrigerant in the bottle, or until the float switch activates and shuts off the recovery machine. The desired amount of refrigerant depends on the specifications of the system, which you can find on the nameplate or the manual of the system.
  12. Close the high-pressure valve on the manifold gauge set and turn off the recovery machine. Disconnect the outlet hose from the recovery bottle and cap it with a protective cap.
  13. Turn on the power supply to the refrigeration system and reconnect it to the power source.
  14. Start the system and let it run for a few minutes to stabilize.
  15. Check the refrigerant charge level by measuring the subcooling or the superheat of the system, depending on the type of metering device you have. Subcooling is the difference between the actual liquid temperature and the saturated liquid temperature at a given pressure. Superheat is the difference between the actual vapor temperature and the saturated vapor temperature at a given pressure. Both subcooling and superheat can be calculated using the PT chart and the thermometer or the clamp.
  16. Adjust the refrigerant charge level by adding or removing refrigerant as needed, using the same procedure as in steps 9 to 12. The optimal refrigerant charge level depends on the specifications of the system, which you can find on the nameplate or the manual of the system.
  17. Verify that the system is operating properly and efficiently by checking the temperature, pressure, and airflow readings, as well as the performance indicators such as cooling capacity, energy consumption, and noise level.

How to Correctly Use the Recovery Bottle

The recovery bottle is a device that collects and stores the excess or contaminated refrigerant from the system. The recovery bottle has a valve that allows refrigerant to enter or exit, and a float switch that automatically shuts off the recovery machine when it reaches 80% of its capacity. The recovery bottle also has a label that indicates the type and amount of refrigerant it contains.

To correctly use the recovery bottle, you should follow these guidelines:

  • Use only approved recovery bottles that are compatible with the type of refrigerant you are using. Do not mix different types of refrigerants in the same bottle, as this can cause chemical reactions, pressure changes, and performance issues.
  • Check the label on the recovery bottle before using it. Make sure that it matches the type of refrigerant you are using, and that it has enough space to accommodate the amount of refrigerant you are transferring. If the label is missing or damaged, do not use the bottle.
  • Connect the recovery bottle to the digital scale and place it on a flat surface. The digital scale will measure the weight of the refrigerant that is transferred to or from the bottle.
  • Connect the recovery bottle to the outlet hose of the recovery machine. The recovery machine will pump refrigerant to or from the bottle, depending on whether you are charging or recovering refrigerant from the system.
  • Open the valve on the recovery bottle and turn on the recovery machine. Monitor the weight reading on the scale and the pressure reading on the gauge. Do not exceed 80% of the capacity of the bottle, as this can cause overfilling and possible explosion of the bottle. The float switch will automatically shut off the recovery machine when it reaches 80% of its capacity, but you should also keep an eye on it as a backup.
  • Close the valve on the recovery bottle and turn off the recovery machine when you are done transferring refrigerant. Disconnect the outlet hose from the bottle and cap it with a protective cap.
  • Update or replace the label on the recovery bottle with accurate information about the type and amount of refrigerant it contains. Store or transport the recovery bottle in a safe and secure place, away from heat sources, sparks, flames, or direct sunlight.

Troubleshooting Common Charging Problems

Charging a refrigeration system with freon gas is not a simple task. It requires proper tools, equipment, procedures, and safety precautions. If done incorrectly, it can cause problems such as reduced cooling capacity, increased energy consumption, compressor damage, environmental pollution, and personal injury.

Some of the common problems that can occur during charging are:

  • System Doesn’t Reach Desired Pressure: If the system pressures are not reaching the desired values, check for restrictions in the refrigerant lines, a faulty expansion valve, or an undercharged system.

  • Frost on Evaporator Coils: Frost formation on the evaporator coils indicates a potential undercharge. Check the superheat values and consider adding more refrigerant if necessary.

  • Excessive Pressure: If the system’s pressure becomes too high, it could be due to overcharging, a faulty condenser fan, or a clogged condenser coil. Reduce the refrigerant charge if overcharging is suspected.

  • Leak Detected: If a refrigerant leak is detected, use a leak detector to identify the source. Repair the leak before proceeding with charging.

  • Inaccurate Pressure Readings: If pressure readings on the manifold gauge set are inaccurate, check for leaks or faulty gauge components.

  • Insufficient Cooling: If the system is not cooling adequately after charging, verify that the superheat and subcooling values are correct. Inadequate cooling could be due to incorrect charging or a malfunctioning component.

In conclusion, charging a refrigeration system with Freon gas is a critical process that requires precision and attention to detail. Properly charging the system ensures its efficiency, performance, and longevity. By following the step-by-step guide outlined in this article, you can confidently navigate the charging process and troubleshoot any issues that may arise. Remember to prioritize safety, adhere to environmental regulations, and seek professional assistance if you encounter complex problems. With the right approach, your refrigeration system will provide reliable cooling for years to come.

If you want to learn and get a “Diploma in Marine Refrigeration and Climate Control”, please follow THIS LINK on Alison platform. The course is free and all you need to do is just to subscribe to their platform using the link above. This will be of a great help to me as well, as I will earn small commission. You can consider this as a reward for my effort to provide guidance and advices with regard to complex, challenging and rewarding marine engineering.

If you wish to learn about “Oil in Refrigeration and Air Conditioning Systems”, please follow THIS LINK.

If you have any questions regarding above, please feel free to use our existing forum Seafarer’s World, Telegram Chief Engineer’s Log Chat or Instagram and will try to answer to all your queries. You can use the feedback button as well!

If you like my posts, please don’t forget to press Like and Share. You can also Subscribe to this blog and you will be informed every time when a new article is published.

Also you can buy me a coffee by donating to this website, so I will have the fuel I need to keep producing great content! Thank you!

Please feel free to leave a reply!